Fire Sprinkler Pipes

BAOLAI provides a comprehensive range of fire sprinkler pipes, engineered for maximum safety and reliability. As a China Top 500 Manufacturer since 1991, we are trusted globally with UL & FM Dual-Certifications and serve over 150 countries worldwide. Our fire pipes feature various coating options—including painting, epoxy, and galvanization—to combat every potential threat.

What Are Fire Sprinkler Pipes?

Fire sprinkler pipes are a critical component of an active fire protection system, designed to carry water or other extinguishing agents to sprinkler heads throughout a building. These pipes must be durable, reliable, and able to withstand the pressures and temperatures associated with fire suppression.

The materials used for fire sprinkler pipings are chosen based on factors such as building type, environmental conditions, and cost. The most common types of fire sprinkler pipe materials are steel, copper, and CPVC. Steel fire protection pipes are the most traditional and widely used material for fire sprinkler systems due to its strength, durability, and resistance to high temperatures. 

UL Listed & FM Approved Fire Sprinkler Pipes

BAOLAI® Fire Sprinkler Pipe Types

EPOXY COATED FIRE SPRINKLER PIPES

Our epoxy-coated pipes offer exceptional corrosion resistance, ideal for long-term fire protection systems.

  • Coating: Powder epoxy coated from 100 to 300 microns.
  • Corrosion Protection: Corrosion category C3-High certified.
  • Color: Available in Red Epoxy (RAL 3000).
  • Lengths: 5.8M, 6M, 12M, and customized options.
  • Pipe Ends: Roll grooved, cut grooved, threaded, coupled, and beveled.
  • Certifications: FM/UL certified.
  • Standards: Produced according to ASTM and UL standards.
  • Durability: Factory direct supply with superior durability.

GALVANIZED (ZINC COATED) FIRE SPRINKLER PIPES

Designed for superior durability and long-lasting performance, our GI Galvanized Fire Sprinkler Pipes are suitable for a wide array of fire suppression systems.

  • Coating: Zinc coated from 30 to 100 microns.
  • Lengths: 5.8M, 6M, 12M, and customized options.
  • Pipe Ends: Roll grooved, cut grooved, threaded, coupled, and beveled.
  • Approvals: FM/UL approved, ensuring the highest safety standards and easy installation.
  • Applications: Ideal for wet, dry, pre-action, and deluge systems.

PRIMER VARNISHED FIRE SPRINKLER PIPES

Our primer varnished fire pipes offer an excellent balance of corrosion protection and cost-effectiveness.

  • Varnishing Thickness: Between 20-200 microns.
  • Colors: Available in Black, Red, Blue, and customized painting.
  • Lengths: 5.8M, 6M, 12M, and customized options.
  • Pipe Ends: Roll grooved, cut grooved, threaded, coupled, and beveled.
  • Versatility: Available in a range of sizes, suitable for a wide variety of scenarios.

Related products

BAOLAI® Fire Sprinkler Pipe Sizes and Specification

Note: Some of the main specifications are shown below, please contact us for more details.

NPS Designator Outside Diameter Nominal Wall Thickness Weight Plain End Test Pressure
Electric Resistance Weld
inch mm inch mm sch lb/ft kg/m Psi Mpa
3/41.05026.70.0832.11100.861.287004.83
0.1132.87401.131.697004.83
11.31533.40.1092.77101.412.097004.83
0.1333.38401.682.507004.83
1 1/41.66042.20.1092.77101.812.6910006.89
0.1403.56402.273.3910006.89
1 1/21.90048.30.1092.77102.093.1110006.89
0.1453.68402.724.0510006.89
22.37560.30.1092.77102.643.9310006.89
0.1543.91403.665.4510006.89
2 1/22.87573.00.1203.05102.645.2610006.89
0.2035.16405.888.6410006.89
33.50088.90.1203.05104.346.4610006.89
0.2165.49407.5811.2910006.89
3 1/24.000101.60.1203.05104.987.4112008.27
0.2265.74409.1213.5812008.27
44.500114.30.1203.05105.628.3712003.05
0.2376.024010.8016.0912008.27
55.563141.30.1343.40107.7811.5812003.40
0.2586.554014.6321.7912008.27
66.625168.30.1343.40109.3013.8510003.40
0.2807.114018.9928.2912008.27
88.625219.10.1884.781016.9625.268004.78
0.2777.043024.7236.8212008.27
1010.750273.10.1884.781021.2331.267004.78
0.3077.803034.7251.0510006.89